Specifications
| AC Input Voltage: | 120, 208, 240, 480 ±10% 60Hz/50Hz, single phase/three phase |
| Input current: | As per Model selected. |
| Output Voltage Regulation: | ±1% maintained with ±10% line voltage and ±5% frequency variation along with load variation of 0-100% |
| Transient Response: | ±5% for 20-100% load change with battery connected |
| Front Panel Current Control: | Current limit adjustable from10-110% |
| Battery Charger Output Ripple: | 200mV rms without a battery connected 30mV rms with a battery Ah 4 times greater than the charger’s output current rating. |
| Operating Environment Conditions: | 32º-104ºF (0-40ºC), 5-95% humidity (non-condensing), below 3300 feet altitude |
| Storage Environment Conditions: | -20º-160ºF (-29-71ºC), • Protection: Input and output circuit breakers rated at 5KAIC 480V input fused at 200KAIC |
| Finish: | RAL 7046 epoxy paint and galvanized |