Power Systems | Energy Storage Products | Converters, Transformers EXODUS P Series - 3 Phase input / 3 Phase output ( 10 - 120 kVA ) - Power Systems | Energy Storage Products | Converters, Transformers
EXODUS P Series – 3 Phase input / 3 Phase output ( 10 – 120 kVA )

Sale!

EXODUS P Series – 3 Phase input / 3 Phase output ( 10 – 120 kVA )

$25,000.00 $20,000.00

The New MAKPOWER EXODUS P Series UPS uses the latest DSP Technology to be programmed to suit wide verity of electrical environments without impending its performance. With the P series range efficiency reliability and functionally are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits at all the UPS subsystems to controlled with greatly increased precision

General Specifications

  • Transformer-less UPS topology
  • Low input current total harmonic distortion (THD)
  • High input power factor
  • High efficiency up to 94%
  • Cold start function
  • Static and maintenance by-pass switch
  • Output short circuit and overload protection
  • External REPO switch input
  • 192 events memory (192 events 4500 alarms)
  • Clock and calendar (battery supported)
  • Automatic battery test, remaining battery time indicator
  • Temperature compensated charge system
  • Regenerative back feed function
  • 2 RS232 serial ports and 12 dry contact outputs
  • 3 DSP controlled modular structure
  • Optional SNMP and MODBUS adaptors
  • Optional Graphical and touch panel
  • 5 years spare parts support
  • Full digital Structure
  • Small footprint
  • Economode operation
  • Fewer electronic components
  • Output current limiting
  • Advanced diagnostics for the input
  • Selectable Input /output /Frequency range
  • Split bypass input(Second Input)
  • Output Dc Leakage Protection
  • Separate DPS for inverter Control
  • Separate DPS for the PFC
  • 3 level battery protections
  • High Charge current capacity
  • Charge /Discharge Current indicator
  • Advanced remote control features

Specifications

Technical Specifications
ModelsEX310, EX315, EX320, EX330, EX340, EX360, EX380, EX3100 ,EX3120
Power (kVA)10, 15, 20, 30, 40, 60, 80, 100, 120
Input
Power factor / THDI>0.98 / <5%
Voltage380-400 VAC 3 Phase ,4 Wires, + Earth ± 20% (240/415VAC +15%, -25% )
Frequency50 Hz / 60 Hz selectable ± 5%
By-pass Voltage380 - 400 VAC 3 Phase ,4 Wires, ± 20%
By-pass ProtectionShort circuit, Voltage tolerance, Frequency tolerance, VA T transfer
Voltage Distortion<10%
ProtectionFuses, Voltage & Frequency tolerance, Input power limit Input PFC
Output
Power(kW)8, 12, 16, 24, 32, 48, 64, 80, 96,
Power factor0,8 ( optional 0,9 )
Voltage380-400 VAC 3 Phase , 4 Wires, + Earth, ± 1%
Frequency50Hz/60 Hz selectable
Frequency toleranceLine synchronized: ± 2% / Free Running: ± 0,2% (adjustable)
Efficiencyup to 94%
Crest Factor3:01
Overload Protection100% - 125% load: 10 min., 125% - 150% load:1 min., >150% load: bypass (adjustable)
Other ProtectionsAdvanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD (at 100% linear load)<3%
Battery
TypeSealed Lead Acid - Maintenance free
Numbers36 VDC, 48 VDC, 72 VDC
Float charging voltage2 x 405 VDC
End of discharge voltage2 x 300 VDC
Battery cabinetInternal, External Cabinet
Battery ambient temp. ºC20 ºC
Protections3 level alarms, Battery fuses, Carhging current limit, Temeperature compensation
Automatic testingStandard every 72 hours (adjustable)
General
RegulationsEN62040-2
User interface4 lines LCD panel, Mimic leEX, 5 vector buttons, Buzzer, Optional graphical touch-panel
IndicatorsP-N voltage, P-P voltage, Current, Power, Crest Factor, Freq uency, PF,Service time
AdvancedSelf diagnostics, 4 maintenance time indicators, Calibration over RS232
Communication2xRS232 serial ports,4 standard and 8 optional DRY contact alarm relays
InputsEPO input, Interactive battery panel input, Genset input
Genset kitStandard( programmable )
SoftwareStandard T Mon UPS Management Software (3 clients + 1 server management)
Alarm loggingStandard: with time & date 192 evnts, (optional 512 events)
ProtectionsPower module over-temperature, Over current, Temperature h igh alarm
Temperature rangePower module over-temperature, Over current, Temperature h igh alarm
Temperature range0ºC -40ºC
Protection degreeIP20
Humidity / Altitude90% max (noncondensed) / <1000m above sea level
Acoustic noise<57 dBA, <62dBA, <64dBA, <68dBA
Weight (kg)113, 113, 124, 170, 195, 175, 185, 380, 374
Dimensions (mm) HxWxD1040x425x805, 1440x515x850, 1900x775x910
Options
Input110/208 VAC
Output110/208 VAC
TransformerGalvanic isolation transformer at the input & output
SoftwareT-Mon Admin Multi UPS monitoring, T-Mon Server 50-100-200 cl ients, DLOG log loader
AdaptorsSNMP, MODBUS, RS485, Remote Panel