Power Systems | Energy Storage Products | Converters, Transformers EXODUS H Series - 3 Phase input / 3 Phase output ( 100 - 300 kVA ) - Power Systems | Energy Storage Products | Converters, Transformers
EXODUS H Series – 3 Phase input / 3 Phase output ( 100 – 300 kVA )

Sale!

EXODUS H Series – 3 Phase input / 3 Phase output ( 100 – 300 kVA )

$25,000.00 $20,000.00

MAKPOWER EXODUS Series are, True online, Double conversion UPS Systems, manufactured with the state of the art, PWM and IGBT technology, producing microprocessor controlled pure sinewave output to critical loads

Features

  • Isolation transformer at the output
  • Advanced LCD alphanumeric display ,mimic lamps and 5 vektor control buttons
  • Interactive RS232 serial port ,3 dry contact alarm relays ,7 optional dry contact relays
  • Maintenance by-pass switch ,static by-pass built in
  • High efficiency up to 91%, cold start from batteries
  • Battery charge current limiting,3 level battery alarms, boost charge system
  • 3 microprocessors: main control system, rectifier system and parallel controller
  • Password protected adjustments menu
  • External remote emergency power off input (REPO)
  • Maintenance bypass switch and indicator
  • Calender and real time clock
  • Rectifier input switch, Output switch, adjustable power walk in delay
  • Programmable overload protection ,output short circuit protection
  • Optional parallel operation
  • Input and output customization, possible
  • Optional SNMP, MODBUS, RS485 adaptor and RS232 multiplexer
  • Monitoring and control software
  • 128 events (4000 alarms) memory with date and time
  • User selectable options

Specifications

Technical Specifications
ModelEX 3100, EX 3120, EX 3160, EX 3200, EX 3250, EX 3300
Power (Kva)100, 120, 160, 200, 250, 300
Input
Power factor ,THDIPF > 0.98 , THD <5%
Voltage230/400 VAC 3 phase ,4 wire , +/-20%
Input Frequency50 Hz or 60 Hz, +/-5%
Voltage distortion<%10
By - pass voltage230/400 VAC 3 phase ,4 wire , +/-20%
EMIEN50091- 2 Class A
ProtectionInput fuses, voltage low and high alarm, input power limiting
Output
Power (Kw)80, 96, 128, 160, 200, 240
Power factor0,8
Voltage / frequency230/400 VAC 3 phase , 4 wires + earth-50 Hz or 60 Hz, +/- %-5
Frequency tolerantSynchron +/- 2% ,free running +/-0,2%
ProtectionOverload, short circuit, voltage low or high ,DC balance protections
AC/AC efficiency90% up to 92%
Crest factor3:1
Overload time100 -125% load 10 mins,125-150% 1 min, >150% by-pass
THD at full load<3%
Battery
Type / quantityMaintenance free ,sealed lead acid type / 32 batteries
Float /discharge end405 VDC / 300 VDC
Battery cabinetExternal cabinet
Ambient temperature25 ºC
ProtectionBattery fuses,3 level alarms ,charge current limit
Aut.Battery testStandard (every 72 hours)
Boost chargeStandard
General
Human interface2 or 4 lines LCD panel, mimic leds ,5 vector buttons
Alarm loggingStandard with time and date ( 128 events,4000 alarms )
Real time clockStandard
CommunicationRS232 serial port , 3 DRY contact alarm relays
Control softwareStandard for 3 clients management
ProtectionsPower module Over temperature, over current protection
Operating temp.0-40 ºC
Protection degreeIP20
Humidity / Altitude90% (non condensed) / <1000 m above sea level
Acoustic noise<50 dBA
Dimensions ( mm) HxWxD1650x1100x800, 1730x1195x870, 1880x1565x925
Weight (kg) 770, 810, 960, 1150, 1285, 1416
Options
AdaptorsSNMP, MODBUS, RS485, RS232 multiplexer,remote panel
Parallel operationN+1 system , redundant system as option
Isolation transformerFor input or output available as option
Battery panelInteractive battery CB available as option
12 pulse rectifier10% input current THD (ask for dimensions)